beautypg.com

Through-the-wall installations, Before after, Top view – Friedrich KM24 User Manual

Page 15

background image

15

920-198-00

STEP 1 Follow steps 1, 2, 3 and 4 of the "STANDARD SASH WINDOW

INSTALLATION" instructions beginning on page 10.

STEP 2 CABINET PREPARATION – Remove the sill plate from the

cabinet by removing the two nuts and screws retaining the sill

plate. Note that the chassis retainer is secured by a right side

nut and screw (See Detail 1, Figure A.) Bend the tabs of the

sill plate down into its channel at both ends of the plate or cut

them off (See Detail 2, Figure A.) Turn the sill plate end to end,

180° and reinstall. Reverse the orientation of nuts and screws

so that the head of screw is on bottom of cabinet facing up and

nut is on top facing down (See Detail 3, Figure A.) Insure that

the chassis retainer is reinstalled as shown in the detail.

Figure A

BEFORE

AFTER

CABINET

SILL

PLATE

TURN SILL PLATE

END TO END

SCREW

(2 REQUIRED)

NOTE: HOLES

MOVED TO

BACK SIDE

NUT

(2 REQUIRED)

RETAINER, CHASSIS

THIS SIDE ONLY

DETAIL 1

BEND TABS DOWN

DETAIL 2

DETAIL 3

SCREW

(2 REQUIRED)

SCREW AND NUT

ORIENTATION NOW

REVERSED

NUT

(2 REQUIRED)

STEP 3 WALL PREPARATION – The maximum wall thickness permis-

sible without special construction is determined by the model size

to be installed. THE OUTSIDE CABINET CONDENSER-AIR-

INTAKE-LOUVERS MUST NOT BE BLOCKED BY EXTENDING

INSIDE THE WALL AREA. Observe the maximum wall thickness

shown in the chart and diagram in Figure B.

SPECIAL INSTRUCTIONS FOR EXTRA THICK WALLS –

For installation in walls exceeding the maximum thickness shown

in the chart, the following suggested construction may apply.

2" MINIMUM

BOTH SIDES

CONDENSER AIR

INTAKE LOUVERS

MAXIMUM WALL THICKNESS

CONDENSER

AIR INTAKE

LOUVERS

TOP VIEW SHOWING

BEVELED SIDES FOR

AIR INTAKE. WALL

BELOW UNIT MUST BE

BEVELED ALSO.

TOP VIEW

CONDITIONED ROOM SIDE AIR

CONDENSER AIR

OUTLET / REJECTED

HEATED AIR

NOTE: Condenser air inlets

and outlet must be unobstruct-

ed to avoid the recirculation of

rejected heated air.

MODEL

A

SMALL CHASSIS

7 ⅜"

MEDIUM CHASSIS

7 ⅜"

LARGE CHASSIS

15 ⅛"

Through-the-wall Installations

The following instructions apply to wood, masonry, brick, concrete or cinder block wall construction

Figure B EXTRA THICK WALL CONSTRUCTION