beautypg.com

Client side map descriptor parameters, Fieldserver specific map descriptor parameters, Driver related map descriptor parameters – FieldServer Gardner Denver FS-8700-60 User Manual

Page 8: Timing parameters

background image

FS-8700-60 Gardner Denver Manual

Page 8 of 12

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

Example

// Client Side Nodes

Nodes

Node_Name , Node_ID , Protocol

, Connection

Node_1

, 1

, Gardner_Denver , P1

Node_2

, 2

, Gardner_Denver , P1

5.3

Client Side Map Descriptor Parameters

5.3.1 FieldServer Specific Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name Name of this Map Descriptor

Up to 32 alphanumeric characters

Data_Array_Name

Name of Data Array where data is to be
stored in the FieldServer

One of the Data Array names from
Section 4

Data_Array_Offset

Starting location in Data Array

0 to (Data_Array_Length-1) as specified
in Section 4.

Function

Function of Client Map Descriptor

RDBC, Passive_Client

5.3.2 Driver Related Map Descriptor Parameters

Column
Title

Function

Legal Values

Node_Name Name of Node to fetch data from

One of the Node names specified in Section 5.2

Gar_Cmd

Data poll commands

Service_Data, Operating_Mode, Operating_Data

Gar_Data*

Data fields in a data poll command
response message. Can be used to poll
for all or specific data or just isolate
specific items in an “All” poll.

Service_Data:
All
, Advisories, Shutdown_codes,
Hourmeter_shutdown, Hourmeter_total,
Hourmeter_loaded, Hourmeter_temp,
Hourmeter_tmp_st, Last_maint_A, Last_maint_B,
Oilage
Operating_Mode:
All
, Oper_mode, Seq_number, Oper_state
Operating_Data:
All, System_pressure, Filter_pressure, Discharge_temp,
Reservoir_temp, Motor_current

5.3.3 Timing Parameters

Column Title

Function

Legal Values

Scan_Interval*

Rate at which data is polled. Note that the Poll_Delay Connection parameter
affects the effective scan interval.

≥0.1s, 0.1s