Example
// Client Side Nodes
Nodes
Node_Name , Node_ID , Protocol
, Connection
Node_1
, 1
, Gardner_Denver , P1
Node_2
, 2
, Gardner_Denver , P1
5.3
Client Side Map Descriptor Parameters
5.3.1 FieldServer Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is to be
stored in the FieldServer
One of the Data Array names from
Section 4
Data_Array_Offset
Starting location in Data Array
0 to (Data_Array_Length-1) as specified
in Section 4.
Function
Function of Client Map Descriptor
RDBC, Passive_Client
5.3.2 Driver Related Map Descriptor Parameters
Column
Title
Function
Legal Values
Node_Name Name of Node to fetch data from
One of the Node names specified in Section 5.2
Gar_Cmd
Data poll commands
Service_Data, Operating_Mode, Operating_Data
Gar_Data*
Data fields in a data poll command
response message. Can be used to poll
for all or specific data or just isolate
specific items in an “All” poll.
Service_Data:
All, Advisories, Shutdown_codes,
Hourmeter_shutdown, Hourmeter_total,
Hourmeter_loaded, Hourmeter_temp,
Hourmeter_tmp_st, Last_maint_A, Last_maint_B,
Oilage
Operating_Mode:
All, Oper_mode, Seq_number, Oper_state
Operating_Data:
All, System_pressure, Filter_pressure, Discharge_temp,
Reservoir_temp, Motor_current
5.3.3 Timing Parameters
Column Title
Function
Legal Values
Scan_Interval*
Rate at which data is polled. Note that the Poll_Delay Connection parameter
affects the effective scan interval.
≥0.1s, 0.1s