FieldServer FS-8700-52 User Manual
Page 7

FS-8700-52 Notifier AM6000
Driver Manual
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: [email protected]
Page 5
4.2 Client Side Connections
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
Baud*
Specify baud rate
2400 (Only baud rate supported by
the Notifier port)
Parity*
Specify parity
Even
Data_Bits*
Specify data bits
7
Stop_Bits*
Specify stop bits
1
Protocol
Specify protocol used
AM6000
Handshaking*
Specify hardware handshaking
None
Poll Delay*
Time between internal polls
0-32000 seconds
default 1 second
Example
// Client Side Connections
Connections
Port, Baud, Parity, Protocol, Data_bits, Handshaking, Poll_Delay
P8, 2400, Even, AM6000, 7, None, 0.100s
4.3 Client Side Nodes
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric characters
Node_ID
Modbus station address of physical
server node
1-255
Protocol
Specify protocol used
Modbus_RTU, Modbus/TCP, etc.
Port
Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
Example
// Client Side Nodes
Nodes
Node_Name, Protocol, Port
Panel1, AM6000, P8