4.2.

Client Side Connection Descriptions

Section Title

Connections

Column Title

Function

Legal Values

Port

Specify which port the device
is connected to the ProtoNode

P1-P8

Protocol

Specify protocol used

TOSHIBA_UPS, TOSH_UPS

Baud*

Specify baud rate

1200–9600, standard baud rates
only (Vendor limitation)

Parity*

Specify parity

Even

Data_Bits*

Specify data bits

7

Stop_Bits*

Specify stop bits

1

Handshaking*

Specify hardware handshaking None

Poll _Delay*

Time between internal polls

0-32000 seconds, 0.05 seconds

Example

//

Client Side Connections


Connections
Port,

Protocol,

Baud,

Parity,

Handshaking,

Data_Bits

Poll_Delay

P1,

TOSH_UPS,

1200,

Even,

None,

7

0.100s

4.3.

Client Side Node Descriptors

Section Title

Nodes

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric characters

Node_ID

Modbus station address of
physical server node

1

Protocol

Specify protocol used

TOSH_UPS, TOSHIBA_UPS

Node_Type

The model of the TIC UPS

1600, 1800, 4200, G8000,
G8000MM, G9000

Connection

Specify which port the device is
connected to the ProtoNode

P1-P8

1

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for

details of the ports available on specific hardware.