Testing the IT-Reference 16 E’s GFCI once a

year is recommended. Simply press the button

marked “GFI TEST.” If the GFCI is functioning
properly, this will cause the main circuit
breaker/power switch to trip and cut off power.

After verifying the GFCI’s proper operation,

simply restore power by switching the Circuit
Breaker/Power Switch to the “1” position.

aC Transient Voltage surge

suppression and Extreme

Voltage shutdown

Extreme Voltage shutdown Indicator:

This LED is normally off. It monitors AC wiring

faults – for example, accidental connection
to an open neutral (in some countries) could
put well over 300 VAC RMS onto the mains
outlet. When the Series Multi-Stage Protection

Plus (SMP+) circuit senses voltages that are
so high that operation would be impossible,
it shuts the power down before damage can

occur. Upon initially applying power to these
units, the Extreme Voltage indicator LED will
light if the input voltage is above the extreme

voltage cutoff, and power will not be applied

to the unit’s outlets. If the unit has been
operating with an acceptable input voltage
and subsequently that voltage exceeds 270

VAC, it will shut off power to the outlet and the

Extreme Voltage LED will light.

Protection oK Indicator:

Although the Furman SMP circuit assures
virtually maintenance free protection from

transient voltage spikes and surges, nature
has a way of occasionally creating electrical
forces that are beyond the capabilities of any

suggested aC Connection