beautypg.com

FieldServer Spectronics FS-8700-42 User Manual

Page 7

background image

FS-8700-42_Spectronics

Driver

Manual

Page

7

of

15


FieldServer Technologies

1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel

: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

4.2.

Client Side Connection Descriptors

Section Title
Connections
Column Title Function

Legal Values

Port

Specify which port the device is connected
to the FieldServer

P1-P8, R1-R2

2

Baud*

Specify baud rate

110 – 115200, standard baud
rates only

Parity* Specify

parity

None

(Vendor limitation)

Data_Bits*

Specify data bits

8

(Vendor limitation)

Stop_Bits*

Specify stop bits

1

(Vendor limitation)

Protocol

Specify protocol used

Spectronics

Handshaking* Specify hardware handshaking

RTS, RTS/CTS, None

Poll Delay*

Time between internal polls

0-32000 s, 1 s

Example

//

Client Side Connections


Connections
Port,

Protocol,

Baud,

Parity,

Handshaking,

Poll_Delay

P8,

Spectronics,

9600,

None,

None,

0.100s

4.3.

Client Side Node Descriptors

Section Title

Nodes

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric
characters

Node_ID

Station address of physical server
node

1-255

Protocol

Specify protocol used

Spectronics

Port

Specify which port the device is
connected to the FieldServer

P1-P8, R1-R2

2

Example:

// Client Side Nodes

Nodes

Node_Name,

Node_ID,

Protocol,

Port

Spec_device1,

1,

Spectronics,

P8

2

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.