Appendix A.4. Connection to York Modbus Microgateway

If connecting the FieldServer to a York Modbus Microgateway, the Node_ID of the
Microgateway is defined by the address DIP switches. If switch 4 is set to ‘On’ and the other
switches are set to ‘off’ then Node_ID of the Microgateway is ‘247’, the parity is ‘Even’, and
the stop bits are 1. Other Node_ID combinations can be found in the York Modbus
Microgateway Installation Manual.