SPECIFICATIONS

Input:

Capacity: 1000VA / 600W

Voltage: +/-25% at line input

Frequency: 50 or 60 Hz +/-10% (auto sensing)

Output:

Voltage (on battery): Simulated sine wave at 110V/115V/120V or

220V/230V/240V +/- 5%

Frequency (on battery): 50 or 60 Hz +/- 5%

AC Line Voltage Regulation:

Input Voltage Range: 90 VAC to 150 VAC

(E-Version Input Voltage Range: 175 VAC to 290 VAC)

Output Voltage Range: 109 VAC to 131 VAC

(E-Version Output Voltage Range: 201 VAC to 252 VAC)

Transfer Time: 2-4 milliseconds, including detection time

Protection and Filtering:

EMI/RFI filter: 10 dB at 0.15 MHz, 50dB at 30MHz

Overload Protection: UPS automatic shutdown if overload exceeds 110% of

nominal at 60 seconds and 130% at 3 seconds

Unit Input: Circuit breaker for overload & short circuit protection

10Base-T Cable Port: Phone/Fax (UTP, RJ-45) compatible jacks

Short Circuit: UPS output cut off immediately or input fuse protection

Batteries:

Type: Sealed, maintenence-free lead acid

Typical Recharge Time: 8 hours to 90% full capacity

Protection: Automatic self test & discharge protection, Replace battery indicator

Back-up Time: 3 - 180 min. (depending on computer load)

Physical:

Net Weight: 26 lbs

Shipping Weight: 29 lbs

Dimension: 14.8” W (19” with rack ears) x 13.8” D x 1.75” H

Alarm:

Battery Back-up: Slow beeping sound (about 0.47 Hz)

Battery Low: Rapid beeping sound (about 1.824 Hz)

Overload: Continuous beeping sound

Interface:

RS-232C port interface: RS-232C Bi-directional communication port

Environment:

Ambient Operation: 3,500 meters max. elevation, 0-95%

humidity non-condensing, 0-40 deg C

Audible Noise: <40dBA (1 meter from surface)