beautypg.com

Five Star Sr200na User Manual

Page 15

background image

• at least 4 feet below or horizontally from, or 1 foot

above, any doors or windows or gravity air inlet to a
building

• At least 3 feet above any forced air inlet located within

10 feet

• At least 4 feet horizontally from electric meters, gas

meters, regulators and relief equipment

• At least 7 feet above grade adjacent to walkways or sim-

ilar traffic areas.

Allow at least 3 feet vertical clearance over vent termina-
tion when terminating under an overhang or deck.
Avoid corners or alcoves where snow or wind could have
an effect. Exhaust may affect shrubbery and some building
materials. Keep shrubbery away from termination. To pre-
vent staining or deterioration, sealing or shielding exposed
surfaces may be required.

FIGURE 14: Typical Special Gas Vent Pipe Installation

(Horizontal-Positive Pressure)

8.

Fire Hazard. Do not run the heater vent

into a common vent with any other appliance. Do not
run the Special Gas Vent into, through, or within any
active vent such as a factory built or masonry chimney.

Table 6: Maximum Vent Length

Final Installation Check:

Check that horizontal vent pipe runs slope uniformly at
least 1/4” per foot to condensate drain(s). No sags, no dips,
no high or low spots.
Check that vent is supported at elbows, tees, and horizon-
tal and vertical runs according to manufacturer’s instruc-
tions and code requirements.

Check that vent supports and wall and ceiling penetrations
allow free movements up, down, and sideways without
putting any strains on the heater or vent body.
Check for at least six (6) inch free air clearance between
the heater vent pipe and combustible materials.
Check that all joints are completely together and sealed.

WATER CONNECTIONS

The heater requires proper water flow and pressure for its
operation. See Figures 15 and 16 for the recommended
installation. The filter pump discharges to the filter, the fil-
ter discharges to the heater, and the heater discharges
directly to the pool or spa.

15

Vent Brand

Wall Thimble

Horizontal Terminal

Vertical Terminal

Saf-T Vent

®

(Part of Vent term.)

5490CI Horizontal Term.

5400 Cap

Saf-T CI Vent

®

(Part of Vent term.)

5490CI Horizontal Term.

5400 Cap

Z-Vent

2SVSWTF04

2SVSTTF04 Tee

2SVSRCF04 Cap

Table 7: Listed Thimbles and Vent Terminals (for Special Gas Vents)

4” Special Gas Vent (Vertical or Horizontal)*

No. of 90° Elbows

Maximum Length

0

50 Ft.

2

40 Ft.

4

30 Ft.

6

20 Ft.

* Minimum vent length is one (1) foot, or in accordance with vent
manufacturer’s instructions, and local and national codes.

Horizontal vents 3’ or less in length do not require a condensate
tee, but must slope down toward the outlet at 1/4” to the foot to
allow condensate to drain.

Condensate
drain w/Trap

Condensate
Tee

2787 0297

Slope at least
1/4" per foot
down towards
condensate drain

Support
weight
of pipe

Listed
Terminal

3" Minimum,
12" Maximum
Clearance

Metal Special
Gas Vent
requires
Appliance
Adapter

Metal

Vent

Body