FS-8700-115 ASCII Driver (General Purpose)

Page 8 of 13

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Other than ‘using up’ point count, there is no danger in setting the
length to a larger number than required.

Poll_Msgs

This parameter allows the user to set the number of times a polling
message should be sent. E.g. If this parameter is set to 3, 3 polls are
issued at a frequency determined by the scan interval. No further polls
are sent even if the Data Array changes.

0 to 2147483647.

Scan_Interval The amount of time between successive poll requests.

0-32000s, 2s