Client side node descriptor parameters – FieldServer FS-8700-66 User Manual
Page 9
FS-8700-66 GE-SNP Driver Manual
Page 9 of 28
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
GE Port Defaults
Parameter
Series 90-30 PLC’s Series 90-70 PLC’s
Baud
19,200
19,200
Data Bits
8
8
Parity
Odd
Odd
Stop Bits
1
1
Max Link Idle Time 10 Secs
5 Secs
GE Port Capabilities
Parameter
Legal Values
Baud
300, 600, 1200, 2400, 4800, 9600, 19200
Data Bits
8
Parity
Odd, Even, None
Stop Bits
1, 2
Max Link Idle Time 1 to 60 Secs
5.2
Client Side Node Descriptor Parameters
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for Node. The driver uses the
Node name to establish a connection with the
Server if the Node_ID is non-zero.
If the Node_ID is zero then the driver ignores
the Node name when logging onto the PLC and
logs on using a Null nameThsu the driver is able
to log onto a Node whose name is unknown.
Up to 32 alphanumeric characters
Node_ID*
The parameter is used in conjunction with
Node_Name to control how the driver logs onto
the PLC
0,1
Protocol
Specify protocol used
SNP
Port
Specify which port the device is connected to
the FieldServer
P1-P8, R1-R2
2
SNP_Longbreak*
Number of characters used to calculate the
time for the specified baud rate at which the
FieldServer will send a break signal to the PLC.
1-65535, 4
SNP_Break_Offdelay*
Delay (in milliseconds) before a message is sent
to the PLC from the FieldServer after the break
is released.
1-65535, 70
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.