Page 16
FS-8700-66 GE-SNP Driver Manual
Page 16 of 28
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
6.3.2 Driver Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch data from
One of the Node names
specified in “Client Node
Descriptor” above
Data_Type
Data type
Use one of the Data Types specified in brackets.
Discrete Inputs (%I)
Discrete Outputs (%Q)
Discrete Temporaries (%T)
Discrete Internals (%M)
Genius Global Data (%G)
Analog Inputs (%AI)
Analog Outputs (%AQ)
Registers (%R)
%SA Discrete
%SB Discrete
%SC Discrete
%S Discrete (%S)
Length
Length of Map Descriptor – may not exceed the table length
in the PLC.
1 - 1000
Address
Starting address of read block / write block
The 1st element of each Data type Table is referred to as
address one.
1 , 2 , 3
Positive whole numbers
6.3.3 Timing Parameters
Column Title
Function
Legal Values
Scada_Hold_Timeout
Specifies time Server side waits before responding to Client that Node is
offline on FieldServer Client side.
>1.0s