Installation Manual of Room Air Conditioner

10

Double-spanner
operation

Fixing of the unit

1. Position of the wall hole

Wall hole should be decided according to installation

place and piping direction.(refer to installation drawings).

2. Making a wall hole

Drill a hole of 120X70mm dia. with a little slope towards

outside.

3. Piping connection

Indoor side

Outdoor side

Thickness
of wall

Wall hole

70mm

(Cross section of wall hole)

Threads on the pipes may be damaged
when tightening if the pipes are not
well aligned.

(1)

Schematic diagram for unit connection

(4)

Pipe connection process

Torque

18 N.m

Pipe Value

6.35mm

Liquid

50 N.m

(2)

Connection pipe dimensions:

9.52mm

Gas

Outdoor uint

3-way Valve

2-way Valve

Indoor unit

Indoor unit

Apply and tighten the nut.

(3)Cautions for pipe connection
Pipes free from twists, deformation, water, dust.
Dedicated tools for each R407C and R410A
should be used and stored separately.
Optimized radii of bends
Insulation to be applied on all gaseous pipes
Flared section free from cracks

Joint

Spanner

Spanner

Nut

Apply refrigeration oil on the end of the pipe to be connected and on the flared section.
Align the pipes to be connected and tighten the nut. (See the figure)
Ensure that no foreign articles enter into the pipes.

Flared pipe connection