beautypg.com

Operation, Cycling, Auxiliary switches – Honeywell MS8120S User Manual

Page 8: Checkout, Ms4120f (120 vac model), Ms4620f; s20230-f (230 vac models), Ms8120f; s2024-f (24 vac models), Spst switches (table 5), Spdt switches (fig. 12)

background image

MS4120F; MS4620F; MS8120F; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS

63-2584—10

8

OPERATION

The actuators are designed for use in Smoke Control

Systems. If power fails, the actuator spring returns to the 0°

position. The actuator mounts flush with the damper box. The

actuator drives from 0° to 95° and spring returns back to 0°.

The actuators are operated by an spst two-position controller.

When using an spst two-position controller, the actuator drives

to the damper fully open position when controller contact

makes and spring returns to the damper fully closed position

when controller contact breaks. The actuator drops to holding

power level on detection of stall, independent of hub position.

Cycling

The actuator and the internal spring are designed so that no

special cycling during long-term holding is required.

Honeywell recommends following all local, state, and national

codes for periodic testing of the entire smoke control system.

Refer to National Fire Protection Association (NFPA) National

Fire Codes

®

: NFPA90A, NFPA92A, and NFPA92B for your

application.

Auxiliary Switches

Some models include auxiliary switches (see Table 1).

SPST Switches (Table 5)

See Fig. 7 through 9 for SPST auxiliary switch wiring.

Table 5. SPST Auxiliary Switch Operation.

NOTE: Both sets of contacts are open when the actuator

is between 7° and 85°.

SPDT Switches (Fig. 12)

See Fig. 10 through 12 for SPDT auxiliary switch wiring.

Fig. 12. SPDT auxiliary switch operation.

CHECKOUT

MS4120F (120 Vac model)

1. Check damper position.

2. Connect 120 Vac to the black and white leadwires to

drive the damper to the open position. The actuator

should drive the damper.

3. If the actuator does not run, remove power for at least

two seconds.

4. If the actuator spring returns, allow it to close entirely,

then return to step 2.

5. If the actuator does not spring return, verify that the

actuator is properly installed. See Installation section.

6. If the actuator is correctly installed but neither runs nor

spring returns, replace the actuator.

MS4620F; S20230-F (230 Vac

models)

1. Check damper position.

2. Connect 230 Vac to the blue and brown leadwires to

drive the damper to the open position. The actuator

should drive the damper.

3. If the actuator does not run, remove power for at least

two seconds.

4. If the actuator spring returns, allow it to close entirely,

then return to step 2.

5. If the actuator does not spring return, verify that the

actuator is properly installed. See Installation section.

6. If the actuator is correctly installed but neither runs nor

spring returns, replace the actuator.

MS8120F; S2024-F (24 Vac models)

1. Check damper position.

2. Connect 24 Vac to the red and black leadwires to drive

the damper to the open position. The actuator should

drive the damper.

3. If the actuator does not run, remove power for at least

two seconds.

4. If the actuator spring returns, allow it to close entirely,

then return to step 2.

5. If the actuator does not spring return, verify that the

actuator is properly installed. See Installation section.

6. If the actuator is correctly installed but neither runs nor

spring returns, replace the actuator.

Switch

Wire

Color

Makes

Breaks

(degrees from fully closed position)

blue

less than 7

greater than 7

85°

yellow

greater than 85

less than 85

BLACK/BLUE

BLACK/RED

BLACK/YELLOW

BLACK/BLUE

BLACK/RED

BLACK/YELLOW

LESS 7°

MORE 7°

GRAY/BLUE

GRAY/RED

GRAY/YELLOW

GRAY/BLUE

GRAY/RED

GRAY/YELLOW

LESS 85°

MORE 85°

7° SWITCH

85° SWITCH

M20679B

This manual is related to the following products: