4-2. TROUBLESHOOTING
(Continued)
Display
Cause
Correction
AL-5
Temperature too low
in the hold mode.
Faulty control board - replace control board.
Faulty contactor - replace contactor.
AL-6
Temperature too high in
the hold mode.
Faulty control board - Replace board.
Door opened too much - Make sure door stays
closed as much as possible.
Problem
Cause
Correction
The evaporator is iced-up
Faulty De-icing Heater
Replace De-icing Heater
after a de-icing cycle.
Evaporator temperature at end
Increase the setting of step 8
of de-icing cycle too low.
in Section 3.
Maximum time of de-icing cycle
Increase the setting of step 7
too short.
in Section 3.
Too much water on evaporator
The unit has been shut down without
Start a de-icing cycle.
fins.
a de-icing cycle.
Slow to decrease
Compressor not working properly
Check compressor and re-
in temperature (decline in
place if neccessary.
performance)
Evaporator fan not working properly
Check the fan and replace if
neccessary.
Temperature of room too high.
Ventilate the room.
Not enough clearance around unit.
Change the location of the
unit. (See section 2-4)