3-5. PROGRAMMING

dS: defrost system (computation); dF=digifrost Feature;

Continued

defrost start time based on total compressor running time
rt=real time; defrost start frequency, based on real time

dI: defrost interval; defrost frequency in hours, based on the

selection of “dS”

dE: defrost endurance; total (maximum) length of a defrost

cycle, expressed in minutes. (1...99 range)

dL: display lock; temperature display is locked during a

defrost cycle (0...31 range)
“n”=no (readout continues to display the actual tempera-
ture, even during a defrost cycle
“y”=yes (readout is locked)

dr: display read-out; select the type of visualization in case of

temperature display lock during defrost (see prameter dL);
“C”=the temperature displayed at the start of a defrost is

locked and does not change during this cycle;

“dF”=during the defrost “dF” is displayed.

do: defrost at power on; selects whether or not, the system

goes through the defrost cycle at start-up (or after power
failure)
“n”=no; “y”=yes

dd: defrost delay at power on; delay of defrost cycle, in

minutes (0...99 range)

Error Code “E1”

This is the only error code in these controls. It indicates a tempera-
ture sensor failure, such as, a shorted sensor, a sensor break, or
absence of sensor.

It can also indicate an under-range in the system temperature (-55).

In case of an over-range in the system temperature, “99” shows first
in the display, followed by “E1”.