3-5. PROGRAMMING

1.

Press and hold for 4 seconds. The “DEF/SET” light

flashes in display.

Temperature Setpoint

2.

Press the

or

to change the temperature setpoint,

within 5 seconds. After 5 seconds, the last entered setpoint
stays in memory.

Other Parameters

3.

Press to access the other parameters. Each press of the

accesses the next parameter. The parameters are:

d: differential (-15...15 range)

LS: lower set; lower user-access setpoint limit
(-55...99 range)

The units are programmed to defrost 3 times a day, at 8 hour
intervals, lasting 30 minutes. Do not program the setpoint
temperature below 33° F (1° C), or ice build-up will decrease
efficiency.

HS: higher set; upper user-access setpoint limit
(-55...99 range)

CA: calibration; temperature readout offset to allow for
possible error due to probe location (-15...15 range)

rP: relay protection; select relay status in case of probe defect.
“on” = compressor on in case of probe defect.
“of” = compressor off in case of probe defect

PS: protection system-short cycle; select type of compressor
protection desired (the actual time delay is set with the next
parameter):

“0”=delay before start - in seconds;
“1”=delay before start - in minutes;
“2”=delay after stop - in minutes;
“3”=delay between starts - in minutes

Pt: protection time; select the time delay setting for compres-

sor protection. (0...31 range)

3-5