Installation

10

Cable connection

XPass D2 can be used as an RFID card reader by connecting to a master device or a CoreStation.

Power supply connection

NOTE

Use a power supply adaptor of DC 12 V (± 10%) with a minimum of 1,500 mA which has obtained the approval of IEC/EN 60950-1. If

you wish to connect and use another device to the power supply adaptor, you should use an adaptor with a current capacity which

is the same or larger than the total power consumption required for the terminal and another device.

RS-485 connection

NOTE

Use an AWG24 twisted pair with a maximum length of 1.2 km for the RS-485 cable.

If connecting with a RS-

485 daisy chain, connect the termination resistor (120 Ω) to both ends of the daisy chain connection. If

connected to the middle line, the signal level becomes smaller and the communication performance will deteriorate. Make sure to

connect it to both ends of the daisy chain connection.

1 - PWR +VDC

Red

2 - GND

Black (White stripe)

3 - 485 TRXN

Yellow (Black stripe)

4 - 485 TRXP

Blue (White stripe)

Control device

XPass D2

DC power

XPass D2

1 - PWR +VDC

Red

2 - GND

Black (White stripe)

DC power