background image

Material

3170 Wasson Road • Cincinnati, OH 45209 USA

Phone 513-533-5600 • Fax 513-871-0105

[email protected] • www.bestobellsteamtraps.com

Bulletin IM-IB18HSIM-0608

Maintenance

All Models of IB18H or IB18S.

Check that steam supply is shut-off. Ensure that all

1.

system pressures are off and trap is cool before
opening.
Remove cover (2) from body (1) by removing the

2.

bolts around the body flange.
Lift the cover and internal mechanism from the body.

3.

Unhook bucket unit (3) from lever assembly (4).

4.

Remove guide pin assembly (7) and lever by undo-

5.

ing the two screws.
Inspect pivot points for wear. Replace as needed.

6.

Inspect valve seat (6) and plug (5) (held by clip to

7.

lever) for wear or damage. Replace if required.
Valve seat can be removed using a socket or closed

8.

(box) end wrench.
Make sure interior of body is clean and free of any

9.

accumulation of dirt.
Inspect vent hole in top of bucket until. Make sure it

10.

is clean and open.
Inspect strainer screen (

11.

IB18S only) for dirt or dam-

age. Replace as needed.
Reassemble in reverse order. Tighten valve seat per

12.

torque table. Installing a new body gasket.
Install and tighten cover bolts in a diagonal pattern

13.

to torque values shown in table.

Typical Installation

Part

No.

Component

Material

1

Body

A48 CL

2

Cover

A48 CL

3

Bucket

304 SST

4

Lever

304 SST

5

Valve Plug

Hard surfaced SST

6

Valve Seat

Hard surfaced SST

7

Guide Pin Assembly

304 SST

8

Cover Gasket

Teflon

9

Strainer

304 SST (IB18S only)

10

Strainer Cap

Carbon Steel (IB18S only)

Shutoff
Valve

Strainer

Union

Dirt Pocket
(Optional)

Test Valve

Shut-off

Valve

Basic installation for IB18H or IB18S with shut-off valves
to isolate trap during testing, inspection or repair.

2

8

4

1

3

6

7

5

9

10

Installation with Bypass

IB18S with Blowdown

built-in

strainer

strainer

blow-out

valve

plug

Alternate installation for
IB18S only with inlet same
side as outlet

This manual is related to the following products: