beautypg.com

Troubleshooting (cont.) – MovinCool CM25 User Manual

Page 53

background image

53

TROUBLESHOOTING (cont.)

Condition

Checking Area

Possible

Cause

Remedy

Self-

Diagnostic

Codes

(Wall

mounted

controller)

Buzzer

Pattern

Unit

does

not

operate

at all.

LCD

displays

self-

diagnostic

codes.

AL

1

Signal is input to

the fire alarm

connection.

Check the fire alarm

signal connection.

(See “Fire Alarm

Connection (Input

Signal) on page 34”.)

To reset: Press

RESET button.

PU

3

Drain hose clogged

(for internal drain

pump).

Check drain hose for

any blockages or

excessive kinks that

may prevent water

flow.

To reset: Press

RESET button.

Drain hose trap

position is too high

to pump up

condensation water

(for internal drain

pump).

Improve hose

installation.

To reset: Press

RESET button.

Internal drain pump

is not working.

Check the internal

drain pump

connection.

Replace drain pump.

To reset: Press

RESET button.