INSTALLATION (cont.)

Warning Signal Connection (Output Signal)

The unit is equipped with a warning signal output relay type (Form-C, normal open

dry contact), which can be used to monitor the failure condition.

Relay contactor is closed when the following condition has occurred:
• Condensation overflows
• Temperature sensor fails
• Cooling function fails
The relay output contactor is rated 5 A at 30 VDC or 5 A at 250 VAC (resistive

load), and it is compatible with various warning devices such as alarm speakers,

light indicators, etc.

Connecting Warning Signal to CM25

WARNING:

1. All electrical work should only be performed by qualified personnel.

Repair to electrical components by non-certified technicians may

result in personal injury and/or damage to the unit.

2. Disconnect power before any electrical installation. Beware that

some residual voltage may remain in the unit immediately after the

power is disconnected.

3. Do not touch the relay board of the unit until the green LED7 is

turned off. Failure to follow this warning may lead to electrical

shock.