3. Installation
3-7
3.4.3 The Maximum Combined Simultaneous Power Consumption
Never exceed the maximum combined simultaneous power consumption.
The following chart shows the maximum power available from the 120V-20A GFCI receptacles
during simultaneous consumption (main terminals and receptacles) for both single or three
phase settings. Values shown in the left column give the maximum current available at the
120V-20A GFCI receptacles compared to the value of the simultaneous current consumption from
the main terminals.
SDG25S SDG45S SDG60S
Single
Phase 120V-20A
GFCI Rcept.
Three Phase
240/480V
Single Phase
240/120V
Three Phase
240/480V
Single Phase
240/120V
Three Phase
240/480V
Single Phase
240/120V
kW kVA kW kVA kW kVA kW
0.0 25.0 14.4 45.0 26.0 63.0 36.5
1.2 20.8 13.2 40.9 24.8 59.0 35.3
2.4 16.7 12.0 36.7 23.6 54.9 34.1
3.6 12.5 10.8 32.6 22.4 50.7 32.9
4.8 8.4
9.6
28.4
21.2
46.6
31.7
SDG100S
Single
Phase 120V-20A
GFCI Rcept.
Three Phase
240/480V
Single Phase
240/120V
kW kVA
kW
0.0 100.0
57.7
1.2 96.0
56.5
2.4 91.9
55.3
3.6 87.7
54.1
4.8 83.6
52.9