Herrtronic

®

MDD Supplement

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

8

www.herrmidifier-hvac.com

Figure 7 - Electrical Compartment

VIII. FACTORY WIRING BETWEEN THE MASTER AND SLAVE CONTROLS

Dependent Controls: Factory Wiring Included the Following:

1. Jumpers between Master terminal strip, terminals 11 & 12 to the Slave terminal strip, terminals 11 & 12. This wiring allows com-

munication from the Master to the Slave via the Master Keypad, utilizing the communication functions of Menu 4 in the Master

menu.

2. Jumpers between Master terminal strip, terminal 2 to the Slave terminal strip, terminal 2. This wiring allows the use of an optional

air flow switch wired to the Slave terminal strip. This wire would negate the use of second air flow switch.

3. For Proportional and Proportional/Integral Control Units Only (See MDD wiring diagram). Wiring from the Master Molex connec-

tor J1, terminals 1 & 2 to the Slave terminal strip, terminals 4 & 5. This wiring passes the humidity sensor or BMS control input

that has been received by the Master to the Slave control board. This allows the Slave to “share” the control input with the Master

and operate in parallel with the Master.

4. For On/Off Control Units Only (See MDD wiring diagram). Wiring from Master terminal strip, terminal 5 to the Slave terminal

strip, terminal 5. This wiring passes the On/Off control signal that has been received by the Master to the Slave control board.

Independent Control: Factory Wiring Includes the Following:

1. Jumpers between Master terminal strip, terminals 11 & 12 to the Salve terminal strip, terminals 11 & 12. This wiring allows

communication from the Master to the Slave via the Master keypad, utilizing the communication functions of Menu 4 in the

Master menu.

IX. TURNING THE MASTER AND SLAVE “ON” AFTER SERVICING THE UNIT

During servicing, the Master and Slave cabinet access doors are typically removed to gain access to the unit. Both of these cabi-

nets have a door interlock switch for safety purposes. Whether the door interlock switches are taped closed or jumped-out during

service, when the tape/jumpers are removed from the interlock switches, and the cabinet access doors are re-installed following

maintenance, BOTH THE MASTER AND SLAVE MUST BE TURNED “ON” at the keypad to put the unit back in service. Both the

Master and Slave must be in the Menu 1 default menu for “on/off” button to work. If only the Master is turned ON, the Slave cabinet

will remain inoperative.

Prevent the unit from operating at only 50% capacity by ensuring that BOTH THE MASTER AND SLAVE ARE

TURNED “ON” after servicing the equipment.

Options for Turning ON/OFF Slave:

1. Use “Slave” On/Off button

2. Use “Master” Keypad to address “Slave” via communications. (Menu #4)

8

2

6

4

12

10

1

3

5

7

11

9

7

5

3

1

2

4

6

8

11

9

12

10

1

3

2

4

6

5

1

3

2

6

5

4

A TRION Company

HERRMIDIFIER

EST

1

003PB

PCB

Control

3

VAC

4

24

50/60 Hz

50 to 600 VAC

2

EST

1

4

3

003PB

50 to 600 VAC

50/60 Hz

24

VAC

Control

PCB

2

FOLLOW TORQUE REQUIREMENTS

LISTED ON THE SIDE OF THE

POWER BLOCK.

WARNING

TO REDUCE THE RISK

OF FIRE, REPLACE

ONLY WITH THE SAME

TYPE 4 AMP FUSE.

WARNING

TO REDUCE THE RISK

OF FIRE, REPLACE

ONLY WITH THE SAME

TYPE 2 AMP FUSE.

SLAVE BOARD

MASTER BOARD

COMMON DISPLAY

MASTER TERMINAL STRIP

SLAVE TERMINAL STRIP

USE COPPER CONDUCTORS ONLY

DISCONNECT THE POWER

CAUTION:

ELECTRIQUE AVANT L'ENTRETIEN

CIRCUIT D'ALIMENTATION

SUPPLY BEFORE SERVICING

ATTENTION:

DECONNECTER DU

CAUTION

USE SUPPLY WIRING

SUITABLE FOR 90°C

Conforms to

CORTLAND, NEW YORK 13045

ETL TESTING LABORATORIES, INC.

ANSI/UL-998

R

LISTED

33964

HUMIDIFIERS

ETL LISTED

HERRTRONIC

SANFORD, NC USA

TRION INC.

AMPS

SER.NO.

MAX.

VOLTS/Ph/Hz

MODEL NO.

DATE

MAX.

LBS/HR

/ /

/ /