Fronius Energy Package User Manual
Page 49
47
EN
Version
Displays the version and serial numbers of the PC boards in the inverter (e.g. for service
purposes)
Grid monitoring:
GMTi
Start-up time of inverter in s
GMTr
Reconnection time in s following a grid fault
ULL
Mean grid voltage over 10 minutes in V
LLTrip
Trip time for long-term voltage monitoring
Grid voltage limits:
UILmax
Upper inner grid voltage in V
UILmin
Lower inner grid voltage in V
Grid frequency limits:
FILmax
Upper inner grid frequency in Hz
FILmin
Lower inner grid frequency in Hz
Q-mode:
Current cos phi power factor setting
(e.g. Constant Cos(phi) / Constant Q / Q(U) characteristic / etc.)
AC power limit:
Max. P AC
Manual power reduction
AC voltage derating:
Status
ON / OFF – Voltage-dependent power reduction
GVDPRe
Threshold at which the voltage-dependent power reduction be-
gins
GVDPRv
Reduction gradient used to reduce the power, e.g.: 10% per volt
above the GVDPRe threshold
Message
Activates the sending of an info message via Fronius Solar Net
Fault Ride Through:
Status – default setting: OFF
If the function is activated, the inverter does not switch off im-
mediately in the event of a short-term AC voltage dip (outside of
the limits specified by the grid supplier), but instead continues
to feed in power for a defined period.
DB min – Default setting: 90%
“Dead Band Minimum” setting in per cent
DB max – Default setting: 120%
“Dead Band Maximum” setting in per cent
k-Fac. – Default setting: 0