Displays the version and serial numbers of the PC boards in the inverter (e.g. for service
purposes)

Grid monitoring:

GMTi
Start-up time of inverter in s

GMTr
Reconnection time in s following a grid fault

ULL
Mean grid voltage over 10 minutes in V

LLTrip
Trip time for long-term voltage monitoring

Grid voltage limits:

UILmax
Upper inner grid voltage in V

UILmin
Lower inner grid voltage in V

Grid frequency limits:

FILmax
Upper inner grid frequency in Hz

FILmin
Lower inner grid frequency in Hz

Q-mode:

Current cos phi power factor setting
(e.g. Constant Cos(phi) / Constant Q / Q(U) characteristic / etc.)

AC power limit:

Max. P AC
Manual power reduction

AC voltage derating:

Status
ON / OFF – Voltage-dependent power reduction

GVDPRe
Threshold at which the voltage-dependent power reduction be-
gins

GVDPRv
Reduction gradient used to reduce the power, e.g.: 10% per volt
above the GVDPRe threshold

Message
Activates the sending of an info message via Fronius Solar Net

Fault Ride Through:

Status – default setting: OFF
If the function is activated, the inverter does not switch off im-
mediately in the event of a short-term AC voltage dip (outside of
the limits specified by the grid supplier), but instead continues
to feed in power for a defined period.

DB min – Default setting: 90%
“Dead Band Minimum” setting in per cent

DB max – Default setting: 120%
“Dead Band Maximum” setting in per cent

k-Fac. – Default setting: 0