Installation – Flowserve BK 212 User Manual
Page 10

10
Attention
■
Only qualified welders certified e. g. according to DIN EN 287 may weld
the steam trap into pressurized lines.
■
Do not insulate the steam trap.
Installation
BK 212
1. The steam trap BK 212 can be installed in any position. In the case of a horizontal
installation, make sure that the cover is at the top.
2. Take care of flow direction. The flow arrow is on the trap body.
3. Consider space required for opening trap. When the trap is installed a minimum
space of 150 mm is required for removing the cover .
4. Remove plastic plugs. They are only used as transit protection.
5. Clean socket-weld ends.
6. Arc-weld trap only manually (welding process 111 in accordance with
DIN EN 24063).
Technical Data
– continued –
Heat Treatment of Welds
After the steam trap has been welded into the pipeline the welds require special heat
treatment (we recommend resistance annealing according to DIN EN 100529).
Remove the regulator before carrying out the heat treatment (see Maintenance).
Annealing must be restricted to the region of the welds.
A
Materials
DIN reference
Body
10CrMo 9 10 (1.7380)
Cover bolts (standard)
21 CrMoV 5 7 (1.7709)
Nuts (standard)
24 CrMo 5 (1.7258)
Special cover bolts and nuts
X 22 CrMoV 12 1 (1.4923)
Regulator
Corrosion-resistant Duo stainless steel
sealing surfaces:
wear-resistant titanium alloy
Other internals
Stainless steel