beautypg.com

Vcb series (concealed applications), Wcb series (recessed wall), Warning – First Co VCB User Manual

Page 3

background image

1) Mounting location must allow enough clearance to permit

the removal of screws that secure the cabinet panels.

2) After selecting the location for the unit, remove the front

panel.

3) Position the unit in its permanent location, making sure it is

level to insure proper drainage and operation, and secure

the unit in place. Two 1/2 inch holes have been provided on

each end of the unit for securing the unit to the wall. It is

recommended that all four mounting holes be used for

proper installation. (Figure 5)

4) Note the 1-1/2" x 4-1/2" indentation in the plastic drain pan

(Figure 3). This area is provided for the supply and return

runouts if they are brought up from below the pan. All piping

must be well insulated to prevent sweating. There is a 0.84"

OD condensate drain connection on the secondary drain

pan suitable to receive a standard 3/4" PVC coupling / elbow.

Remove or cover the secondary drain pan before solder-

ing the supply and return coil connections as hot solder

or the torch flame may damage the pan.

5) Solder the 5/8" coil connections in accordance with local

codes and regulations.

6) After coil connections have been made, check for leaks and

bleed the air from the system by venting each coil. (Figure 4)

7) Refer to catalog data for the particular unit to make sure that

the external static pressure of the duct and grille are within

the limits of the unit. The duct should be designed for

velocities in accordance with the methods outlined in the

ASHRAE guidebooks.

It is recommended that airborne noise be controlled with

sound absorbing materials and by installing a flexible con-

nection between the unit and ductwork.

8) Replace the front panel and secure with screws.

VCB SERIES (concealed applications)

Figure 5

WCB SERIES (recessed wall)

1) Mounting location must allow enough clearance to permit

the removal of all mechanical parts within the unit.

2) Frame the unit as required so the front panel of the wall unit

will be flush with the drywall surface when installed.

3) Frame around the perimeter of the unit as required for

securing the drywall. See figure 6 for required drywall

openings for each unit.

Remove or cover the secondary drain pan before solder-

ing the supply and return coil connections as hot solder

or the torch flame may damage the pan.

6) Solder the 5/8" coil connections in accordance with local

codes and regulations.

7) After coil connections have been made, check for leaks and

bleed the air from the system by venting each coil. (Figure

4)

8) After drywall has been installed recheck to make sure the

unit's front panel is flush with the exterior drywall surface.

If not, shimming the unit may be required to obtain a seal

between the unit and wall panel.

9) Install the wall panel to the front of the unit using the 1/4-20

x 1-1/2" long painted Phillips head screws (4 or 6 depend-

ing on the unit size). 1/4" cage nuts are located in the slotted

front panel of the unit for the panel screws to attach to.

Tighten the screws until the panel is secure with a good fit

against the wall.

10) Filter change / replacement can be performed by removing

the lower return air grille to access the filter within the unit.

****** WARNING ******

Proper framing and unit location is critical for unit

performance. Wall panel is required to seal against

the unit panel so there is no air leakage.

4) Mount the unit in its permanent location, making sure it is

level to insure proper drainage and operation, and secure

the unit in place. Two 1/2 inch holes have been provided

on each end of the unit for securing the unit to the studs. It

is recommended that all four mounting holes be used for

proper installation. (Figure 5)

5) Note the 1-1/2" x 4-1/2" indentation in the plastic drain pan

(Figure 3). This area is provided for the supply and return

runouts if they are brought up from below the pan. All piping

must be well insulated to prevent sweating. There is a 0.84"

OD condensate drain connection on the secondary drain

pan suitable to receive a standard 3/4" PVC coupling /

elbow.

-3-

Figure 6

MODEL

NUMBER

DRYWALL CUT-OUT DIMENSION

HEIGHT x WIDTH

3WCB

28" x 42"

4WCB

28" x 50"

6WCB

28" x 58"

8WCB

28" x 66"

10WCB

28" x 74"

12WCB

28’ x 82"

This manual is related to the following products: