Product Overview

Embedded PC

25

Technical Data CX1100-0002 / CX1100-0003

Local I/O signals are connected via the CX1100-0002 power supply variant, to which all Beckhoff Bus Terminals can
be connected, or via CX1100-0003, which in addition to the Bus Terminals enables the connection of Extension Box
IExxxx type Beckhoff Fieldbus Box modules. The option to connect Bus Terminals or a Fieldbus Box creates a
control system with a very variable, expandable I/O level with large signal variety. The I/O data are stored in a
DPRAM, which is accessible by the CPU via the system bus. The power supplies of the CX system can be changed
in the field.

Technical Data

CX1100-0002

CX1100-0003

Power supply

24 V DC (-15%/+20%)

Dielectric strength

500 Veff (supply / internal electronics)

Max. power consumption

30 W

Recommended fuse at 24 V

2 A

K-Bus connection

yes (adapter terminal)

IP-Link connection

-

yes

Connection type

Cage Clamp (adapter terminal)

NOVRAM

8 kByte

Display

FSTN display 2 lines x 16 characters of text, illuminated

I/O-DPRAM

2 kByte

4 kByte

Diagnostics LED

1 x PWR, 1 x I/O Run, 1 x I/O Err

Dimensions

39 mm x 100 mm x 91 mm

58 mm x 100 mm x 91 mm

Weight approx.

250 g

330 g