Settings dip switches rs422 – BECKHOFF CX1000 User Manual
Page 25
Product Overview
Embedded PC
23
RS485 without Echo, Drop-Point ( without Termination)
DIP
Status
Function
1
off
Echo on
2
on
Echo off
3
on
Auto send on
4
off
Always send on
5
off
Auto receive on
6
on
Always receive on
7
off
Term on
8
off
Term on
RS485 with Echo, Drop-Point ( without Termination)
DIP
Status
Function
1
on
Echo on
2
off
Echo off
3
on
Auto send on
4
off
Always send on
5
off
Auto receive on
6
on
Always receive on
7
off
Term on
8
off
Term on
Settings DIP Switches RS422:
RS422 full duplex end point
DIP
Status
Function
1
on
Echo on
2
off
Echo off
3
off
Auto send on
4
on
Always send on
5
off
Auto receive on
6
on
Always receive on
7
on
Term on
8
on
Term on
The dip switches for the configuration of the RS485/422 interfaces can be found at the left side of the module. If you
remove the grey cover you can see the switch.