beautypg.com

4 function description, 1 integrated protection mechanisms, 2 functions – Pilz PNOZ m EF PDP Link User Manual

Page 11: 3 system reaction time, Section 4, Function description, Integrated protection mechanisms, Functions, System reaction time, 4function description

background image

Function description

Operating Manual PNOZ m EF PDP Link
1003019­EN­02

11

4

Function description

4.1

Integrated protection mechanisms

The relay conforms to the following safety criteria:

}

The circuit is redundant with built­in self­monitoring.

}

The safety function remains effective in the case of a component failure.

4.2

Functions

The link module PNOZ m EF PDP Link is used to safely transfer the input information from
decentralised modules to the control system PNOZmulti 2.

The function of the inputs and outputs on the control system depends on the safety circuit
created using the PNOZmulti Configurator. A chip card is used to download the safety cir­
cuit to the base unit. The base unit has 2 microcontrollers that monitor each other. They
evaluate the input circuits on the base unit and expansion modules and switch the outputs
on the base unit and expansion modules accordingly.

The LEDs on the base unit and expansion modules indicate the status of the configurable
control system PNOZmulti.

The online help on the PNOZmulti Configurator contains descriptions of the operating
modes and all the functions of the control system, plus connection examples.

Data exchange:

}

Communication with the decentralised modules is via a safe data link.

}

The link module PNOZ m EF PDP Link reads the input information from the decentral­
ised modules as part of each cycle and then forwards it to the base unit.

}

At the end of a PNOZmulti cycle, the base unit sends its output data to its link module.
This output data is immediately sent to the decentralised modules.

Linking several decentralised modules:

}

A maximum of 4 link modules can be connected to a base unit PNOZmulti 2.

}

A maximum of 4 decentralised modules can be connected to a link module PNOZ m EF
PDP Link.

}

If a decentralised module receives data intended for a different decentralised module
that is connected, the data is forwarded without being processed.

4.3

System reaction time

Calculation of the maximum reaction time between an input switching off and a linked out­
put in the system switching off is described in the document "System Expansion".