Spectrum Controls 1734sc-IE2CH User Manual
Page 45
Chapter 4: IExCH and HART
4-5
User’s Manual Pub. 0300257-01 Rev. A
3. Every 2 minutes if bit remains set.
The following table describes the class, service code and instances required to send the
Read Additional Device Status message.
Table 4-1 (Read Additional Device Status)
Unconnected Message
Field
Value
Definition
Message Type
“CIP Generic”
Service Code
0x4C
Read Additional Status
Class Name
0x035D
HART Object
Instance 0
1-4
Selects All Channels
Selects channel 0-3
Object
Attribute
None, leave this field blank
Request Size
0
No Request Data
Reply Size
2-112 bytes
(2) Size when information not available
(Instance 1-4)
(28) Up to this Size when valid
Information returned for a single
channel (Instance 1-4)
(56 if IE2CH) Fixed size returned for Instance
0
(112 if IE4CH) Fixed size returned for Instance
0
Number of Data bytes
returned
The following tables describe the possible message responses.
Table 4-2 (Request Data)
HART Read Extended Status - Request packet structure
Offset
Field
Value
Definition
No Request Data
Table 4-3 (Request Failed)
HART Read Additional Status - Reply packet structure
Offset Field
Value
Definition
0
Status 34 = DR_RUNNING
(No Device or
connection process
not completed or re-
gathering device
info is in progress)
35 = DR_DEAD
(Channel is not HART
enabled)
Command status
1 Pad
0
Pad
byte