beautypg.com

Spectrum Controls 1734sc-IE2CH User Manual

Page 45

background image

Chapter 4: IExCH and HART

4-5

User’s Manual Pub. 0300257-01 Rev. A

3. Every 2 minutes if bit remains set.

The following table describes the class, service code and instances required to send the
Read Additional Device Status message.

Table 4-1 (Read Additional Device Status)

Unconnected Message

Field

Value

Definition

Message Type

“CIP Generic”

Service Code

0x4C

Read Additional Status

Class Name

0x035D

HART Object

Instance 0

1-4

Selects All Channels
Selects channel 0-3

Object
Attribute

None, leave this field blank

Request Size

0

No Request Data

Reply Size

2-112 bytes
(2) Size when information not available
(Instance 1-4)
(28) Up to this Size when valid
Information returned for a single
channel (Instance 1-4)
(56 if IE2CH) Fixed size returned for Instance
0
(112 if IE4CH) Fixed size returned for Instance
0

Number of Data bytes
returned

The following tables describe the possible message responses.

Table 4-2 (Request Data)

HART Read Extended Status - Request packet structure

Offset

Field

Value

Definition

No Request Data

Table 4-3 (Request Failed)

HART Read Additional Status - Reply packet structure

Offset Field

Value

Definition

0

Status 34 = DR_RUNNING

(No Device or
connection process
not completed or re-
gathering device
info is in progress)
35 = DR_DEAD
(Channel is not HART
enabled)

Command status

1 Pad

0

Pad

byte

This manual is related to the following products: