Factory default settings, Tdm installation – Parr Instrument TDM User Manual
Page 6

TDM Installation
P a r r I n s t r u m e n t C o m p a n y
6
Keys command:
1. Press “SET” to select
2. Press return key move to next operation mode
3. Up/Down arrow keys to adjust value or select type
Main Screen: SP = 0
Press return key and release
Press and hold down “SET” for 5-sec
* RTU if using Specview
** 8 if using Specview
Factory Default Settings
TDM Module
Operation Mode
Select type/value
Comment
r-S
Run
Run/Stop
SP
0
Decimal point position
LoC
OFF
Lock mode (lock all keys or only up/down arrow able to use)
Out1
- (read-only)
Motor output %
Operation Mode
Select type/value
Comment
InPt
v5
Input type (v5 = 0-5V, v10 = 0-10V, nA0 = 0-20mA, nA4 =
4-20mA, nV =0-50mV)
tP-H
2206
Upper-limit range
tP-L
0
Lower-limit temperature range
CTRL
PID
Control mode (ON/OFF, MANUAL, PID and PID PROG)
S-HC
Heat
Heat/Cool control
ALA1
0
Alarm mode
SALA
OFF
System alarm
CoSH
ON
Communication write function that able to use set point from
software
C-S1
ASCII*
Format type
C-no
2
Communication address
bPS
9600
Communication baud rate
Len
7**
Data length setting
PrtY
Even
Parity bit setting
StoP
1
Stop bit setting