Technical specifications, Installation – Inovonics FA401 User Manual
Page 3

© 2001 INOVONICS Wireless Corporation
3
02305C LIT-FA401-INSTALL 8-Oct-01
Technical Specifications:
Dimensions (housing):
6.38" x 3.60" x 1.10"
Weight:
6.9
oz.
Environmental:
Operating
temperature:
32
°
-140F (0
°
-60
°
C)
Relative Humidity:
95% (non-condensing)
Electrical:
Power Requirement:
11-14 VDC
Power Consumption:
120mA (max, relays activated)
Typical:
40mA
(quiescent)
FA401R output relay
Form C, 2A @ 120VAC, 2A @ 300VDC
Receiver:
Type:
frequency-hopping spread spectrum
Operating frequency:
902-928 MHz
The
VALID DECODE LED
indicates transmissions from transmitters programmed to the receiver.
The receiver programs the transmitter with the following fixed parameters:
•
No EOL resistor.
•
No Internal Contact. (The receiver will not support the FA200W or FA210W widegap internal magnet
contact.)
•
60-second supervisory check-in. (The transmitter sends a supervisory signal every 60 seconds. Some
transmitters check in at 150-second intervals.) The receiver, with a fixed 60-minute supervisory
window, will declare the point inactive if no supervisory signal is received within 1 hour of the latest
signal.
•
The Fault Output is Latching for low battery or tamper faults. It is Follower for Inactive faults.
•
The Alarm Output is Follower (follows the state of the transmitter).
Note: FA transmitters have non-volatile memory. It is not necessary to reprogram transmitters after losing
power or changing batteries. Press the transmitter reset button to restore programming.
Installation:
Power: Supply power and ground to terminals marked 13.6V and GND on the terminal block.
Mounting: Use supplied hardware to attach FA401 or FA401R housing to wall or surface. To route wiring
out the back of the unit, use a small flat screwdriver or utility knife to remove the knockout in the housing
base. If possible, orient the antenna side of the receiver toward the transmitter. This enhances reception.
Opening the housing:
ACTIVATED
TAMPERED
LOW BATTERY
INACTIVE
Frequency Agile
Receiver
by Inovonics Corporation
Insert a small flat screwdriver
behind pry point indicator nubs
on top or bottom of the housing
cover (4 places). Gently pry or
twist the housing cover apart.
Reset Button Access Cover:
Insert small screwdriver
in slot on left side. Hold cover
lightly while prying. Install by
inserting top latch and