The Sensor Connections guide lists most common Banner and non-Banner sensors and how to wire them to the DX80

devices.

This reference guide lists typical connections. If you have additional questions about a specific sensor or its connection

instructions, please contact Banner Engineering or the manufacturer of the sensor you are using.

Discrete Sensors. Neither the inputs nor the outputs on the DX80 devices are isolated. Under certain operating

conditions, externally powered sensors may need to have ground in common with the DX80 device to which they are

connected. The power sources do not have to be the same.

Analog Sensors. For analog sensors, the ground/dc common of the sensor should be connected to the ground of the

DX80 device. For best results, Banner recommends that the power source for the sensor and DX80 device is the same.

Discrete Inputs

Discrete Sensors. Neither the inputs nor the outputs on the DX80 devices are isolated. Under certain operating

conditions, externally powered sensors may need to have ground in common with the DX80 device to which they are

connected. The power sources do not have to be the same.

Discrete Inputs, Sourcing

Two-Wire Sensors

Three-Wire Sensors

Discrete IN

PWR

10-30V dc

Discrete IN

GND

dc common

PWR

10–30V dc

Wiring diagram for a sourcing (PNP), two-wire sensor

powered using the SureCross device terminal block.

The sensor's power source might need to be the same as

the SureCross device power source.

Wiring diagram for a sourcing (PNP), three-wire sensor

powered using the SureCross device terminal block. Under

certain conditions, the dc commons between the sensor and

the SureCross device might need to be connected.

The sensor's power source might need to be the same as

the SureCross device power source.

Discrete Inputs, Sinking

Two-Wire Sensors

Three-Wire Sensors

Discrete IN

GND

dc common

Discrete IN

GND

PWR

10-30V dc

dc common

Wiring diagram for a sinking (NPN) two-wire sensor

powered using the SureCross device terminal block. Under

certain conditions, the dc commons between the sensor and

the SureCross device might need to be connected.

Wiring diagram for a sinking (NPN) three-wire sensor

powered using the SureCross device terminal block. Under

certain conditions, the dc commons between the sensor and

the SureCross device might need to be connected.