Bryant 549B User Manual
Page 118

118
PERFORMANCE DATA — 549B, 549C (cont)
ELECTRIC HEATING CAPACITIES — 549B036-120 AND 549C024-060 (cont)
*Two heater packages required to provide kW indicated.
NOTES:
1. The rated heater voltage is 240 and 480 v. If power distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW
new
= Heater kW
rated x
(unit power distribution voltage/rated heater voltage)
2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW
new
= 16 kW (215/240)
2
kW
new
= 12.8 kW (rating at 215 v)
MULTIPLICATION FACTORS
NOTE: The following equation converts kW of heat energy to Btuh:
kW x 3.413 = Btuh.
EXAMPLE: 34 kW (at 230 v) heater on 208 v
= 34.0 (.751 mult factor)
= 25.5 kW capacity at 208 v.
OUTDOOR SOUND POWER (TOTAL UNIT)
UNIT
549B
VOLTAGE
(60 Hz)
ACCESSORY
kW
ACCESSORY
HEATER
PART NUMBER
CRHEATER---A00
ACCESSORY SINGLE
POINT BOX PART NO.
CRSINGLE---A00
090
(7
1
/
2
Tons)
208/230/240
(3 phase)
7.8/ 9.6/10.4
117
007
12.0/14.7/16.0
110
007
18.6/22.8/24.8
111
009
24.0/29.4/32.0
112
009
31.8/39.0/42.4*
112,117
013
460/480
(3 phase)
12.8/13.9
116
006
15.2/16.5
113
006
25.6/27.8
114
008
30.4/33.0
115
008
38.4/41.7*
114,116
—
102
(8
1
/
2
Tons)
208/230/240
(3 phase)
7.8/ 9.6/10.4
117
012
12.0/14.7/16.0
110
012
18.6/22.8/24.8
111
015
24.0/29.4/32.0
112
015
31.8/39.0/42.4*
112,117
017
460/480
(3 phase)
12.8/13.9
116
011
15.2/16.5
113
011
25.6/27.8
114
014
30.4/33.0
115
014
38.4/41.7*
114,116
016
120
(10 Tons)
208/230/240
(3 phase)
7.8/ 9.6/10.4
117
012
12.0/14.7/16.0
110
012
24.0/29.4/32.0
112
015
31.8/39.0/42.4*
112,117
017
37.6/46.2/50.0*
112,110
017
460/480
(3 phase)
15.2/16.5
113
011
25.6/27.8
114
014
30.4/33.0
115
014
38.4/41.7*
114,116
016
46.0/50.0*
115,113
016
HEATER RATING
VOLTAGE
ACTUAL HEATER VOLTAGE
200
208
230
240
380
440
460
480
550
575
600
240
0.694
0.751
0.918
1.000
—
—
—
—
—
—
—
480
—
—
—
—
0.626
0.840
0.918
1.000
—
—
—
600
—
—
—
—
—
—
—
—
0.840
0.918
1.000
549B,
549C
ARI
RATING
(decibels)
OCTAVE BANDS; Lw (A)
63
125
250
500
1000 2000 4000 8000
024,036,048
76
50.8 63.4 62.2 65.9
69.2
65.9
63.0
56.5
060,072
80
57.6 70.2 66.9 71.7
74.7
72.2
67.8
62.4
090
82
62.3 69.3 71.5 74.7
76.2
72.9
68.7
61.5
102
84
64.6 71.1 73.3 76.9
77.6
73.7
70.6
63.7
120
84
64.6 71.1 73.3 76.9
77.6
73.7
70.6
63.7
ARI
— Air Conditioning and Refrigeration Institute
Lw (A) — Unit A — Weighted Sound Power Level
549B
, 549
C