Troubleshooting ge x13-series ecm2.3, Motors, Cont’d – Bard Single Package Air Conditioners PA13362-A User Manual

Page 24

background image

Manual 2100-467K

Page

24 of 24

FIGure 11

trOubleshOOtInG Ge x13-serIes ecm2.3

mOtOrs

cOnt’D.

Model X13 Communication Diagnostics
The X13 motor is communicated through 24 VAC low voltage
(Thermostat Control Circuit Wiring).

1.

Start with unit wiring diagram to confirm proper

connections and voltage (see Figure 11).

2.

Initiate a demand from the thermostat and check the

voltage between the common and the appropriate motor

terminal (1-5). (“G” input is typically on terminal #1, but refer
to wiring diagram!)
a. If the low voltage communication is not present, check
the demand from the thermostat. Also check the

output terminal and wire(s) from the terminal strip or
control relay(s) to the motor.

b. If the motor has proper high voltage as identified

above (Motor not Running #1), and proper low voltage
to a programmed terminal, and is not operating, the
motor is failed, and will require replacement.

Manual

2100-467H

Page

23 of 23

FIGURE 11

TROUBLESHOOTING GE X13-SERIES ECM2.3

MOTORS

CONT’D.

Model X13 Communication Diagnostics

The X13 motor is communicated through 24 VAC low voltage

(Thermostat Control Circuit Wiring).

1.

Start with unit wiring diagram to confirm proper

connections and voltage (see Figure 11).

2. Initiate a demand from the thermostat and check the

voltage between the common and the appropriate motor

terminal (1-5). ("G" input is typically on terminal #1, but

refer to wiring diagram!)

a. If the low voltage communication is not present, check

the demand from the thermostat. Also check the

output terminal and wire(s) from the terminal strip or

control relay(s) to the motor.

b. If the motor has proper high voltage as identified

above (Motor not Running #1), and proper low voltage

to a programmed terminal, and is not operating, the

motor is failed, and will require replacement.

24VAC "R" Sig nal thro ug h

thermo stat o utp ut.

24VAC Co mmo n

24VAC Co mmo n

24VAC "R" Sig nal thro ug h

thermo stat o utp ut.