Fault finding, En 1 9 – SEIFERT Variable Speed Air Conditioner KG 2025-24V User Manual
Page 19

E
N
1
9
6. Fault Finding
FAULT
REASON
SOLUTION
Air conditioner does
not start
Power supply not or incorrectly connected
Connect the power supply correctly
Temperature in the control cabinet is below
the target value.
Wait until the temperature target value is
exceeded. The air conditioner will start by itself.
If the target value of the control cabinet
temperature is too high set a lower target value
Door contact open
Close the enclosure door or bridge door contact
connections.
Air conditioner doesn’t
cool the air
Compressor faulty
The compressor must be
changed. This process must
be carried out by the
manufacturer.
Compressor protection switch has been
activated
Check cooling capacity. If the cooling capacity is
too low at the operating conditions find another
location with lower ambient temperatures or
install an additional air conditioner
Evaporator and/or condenser are heavily
soiled or blocked
The evaporator and/or compressor must be
cleaned
The cooling output of the air conditioner is
too low for the heat generated by the
components in the control cabinet
Check cooling capacity. If the cooling capacity is
too low at the operating conditions find another
location with lower ambient temperatures or
install an additional air conditioner
Evaporator iced up
Insufficient refrigerant due to refrigerant loss
through leaks in circuit
Refrigerant circuit must be
sealed and refilled. This
process must be carried out
by the manufacturer.
The ambient temperature is far below the
lower operating limit.
Place the air conditioner in an area where the
temperature remains within the operating limits
The enclosure is not sealed
Seal the enclosure
Fan or fan capacitor cold side defective
Replace fan and/or fan capacitor
Heavy condensation
Enclosure door is not completely closed
Close the door
Enclosure is not sealed
Seal the enclosure
Incomplete seal at the contact surfaces
between air conditioner and enclosure
Seal the contact surfaces and stiffen the
mounting surface of the enclosure if necessary
Uneven temperature
distribution in the
control cabinet
Enclosure air intake and outlet blocked or
partially impeded by components inside
Move components or change position of air
conditioner
Enclosure volume too large for air
conditioner
Check cooling capacity. If the cooling capacity is
too low at the operating conditions find another
location with lower ambient temperatures or
install an additional air conditioner
Short circuit of the air
Change the air guidance
Condenser fan does
not run
Fan defective
Replace fan