air outlet

are not partially or completely blocked by obstructions in the cabinet .

Sealing


To guarantee that the unit works perfectly ensure that:

the control cabinet is completely sealed (to min. IP54 to EN 60529).

a good seal exists between the control cabinet and the unit.

4.2 Mounting instructions

Danger
Danger from electrical voltage.
Ensure that for the duration of the mounting operation the cabinet is
disconnected from the electrical supply. Therefore take the cabinet out of
operation, following the relevant instructions, before mounting work begins and
take all precautions to prevent premature reconnection of the cabinet.


When all mounting preparations are complete the actual mounting operation can commence.

The resistance of the ground connection between cabinet and cooling unit must be <0.1Ω.

To mount the unit:

Mark the centreline of the unit on the cabinet.
Align the provided template with the centreline on the cabinet.
Mark the cabinet as the on the provided template.
After having checked the dimensions cut the cabinet.
Fix the provided gaskets to the unit before fixing to the cabinet.

4.3 Electrical connection


Danger
Danger from electrical voltage
The unit should only be connected by qualified electricians. The personnel
must ensure that the unit is disconnected form the electrical supply for the
duration of connection work and is protected against unauthorized
reconnection.


Instruction
Check that the available voltage and fuse rating are the same as those stated on the unit data label.