SECTION 9 MAIN ELECTRICAL SERVICE
INSTALLATION
CAUTION: HAZARD OF ELECTRICAL SHOCK
9.1 All wiring must comply with the National Electrical Code. State and Local
Ordinances, and be wired by a qualified electrician.
9.2 Electrical service MUST be connected to a separate 20 AMP, 120 VAC, 60
HZ single phase circuit.
9.3 Electrical service connections are made in the electrical junction box on the
back or side of the heater.
9.4 The heater must have a safety equipment ground from the main electrical
service, stranded 12 GA minimum.
9.5 The electrical conductors for electrical service to the heater MUST be
stranded 12 GA minimum.
9.6 Install a manual service disconnect near the heater, and label its function.
9.7 The supply voltage must be maintained at a minimum 110 VAC.
9.8 The electrical conductors from the main electrical service must be within
approved conduit.
9.9 Keep all electrical conductors and conduit away from the chimney
connector as well as any other hot surfaces. Refer to Section 18 Wiring
Diagram for color code, etc. Keep the power off until the heater is ready to
be started. Refer to Section 13 Start Up Procedure.