Installation – Fulton Classic ICX or FB-F Vertical Tubeless Boilers (Hot Water), Gas_Oil Fired User Manual
Page 9
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 2
ICW-IOM-2014-0410
INSTALLATION
2-3
TABLE 1- DIMENSIONS- REFER TO FIGURE 1
Model ICW
6
10
15
20
30
Unit Size BHP
6
10
15
20
30
A. Boiler Height
IN
MM
57.5
1461
63.5
1613
69.5
1765
72.5
1842
82.5
2096
(B) Boiler Height with Trim* and Fuel Train Assembly
IN
MM
75
1905
80.5
2045
86.5
2197
92.5
2350
102
2591
(C) Overall Depth Stack to Burner Fan Housing
IN
MM
44
1118
46
1168
47
1194
60
1524
67
1702
(D) Boiler Diameter
IN
MM
26
660
28
710
30
760
39
990
46
1170
(E) Flue Outlet Diameter
IN
MM
6
152
6
152
8
203
10
254
12
305
(F) To Center of Flue Outlet
IN
MM
52
1320
58
1473
63
1600
66
1675
73.5
1867
(G) Return Water Inlet Height
IN
MM
15.5
394
16
406
16.25
413
17.25
438
17.5
445
(H) Overall Width
IN
MM
31
787
33
838
35
889
42.5
1080
50.5
1283
(I) Gas Train Extension (CSD-1)
IN
MM
22.5
572
21.5
546
20.5
521
25
635
27
686
(J) Clearance Required for Trim & Burner Removal*
IN
MM
82
2082
86
2184
92
2337
96
2438
106
2692
*This dimension is 6 inches (152.4 mm) less for oil fi red units.
F
D
C
K
A
J
B
G
O
M
E
H
L
N
I
Side View