Operation, Wiring, System variations: humidity control - standard – GeneralAire DH95 Dehumidifier User Manual
Page 5: Unit schematic

5
When a remote Humidistat is utilized, set the unit mounted humidistat to the
“OFF” position.
Typical Equipment Layout Specification & Duct Connection
Operation
The DH95 is designed to deliver dehumidified, filtered air to the living space, and is equipped with an onboard
humidistat and fan control and can be equipped with various accessories to enhance its operation, including a
remote humidistat, and your system may incorporate any or all of the described operational components
It is recommended that the indoor environment maintain a maximum relative humidity level of 50% to
60%. Other factors may dictate a relative humidity level different than the recommended, such as musical
instruments, antiques, books/papers, or special situations. Winter minimum humidity levels of 30-35% may
not be attainable without supplemental humidification (Humidifier), and may not be desired during times of low
outdoor temperatures.
System Variations:
Humidity Control - Standard
The system may be installed as free standing or incorporate ducting to an area or existing heating/cooling
system. Control is provided by Humidistat with a dial stem type adjustment built into the unit. Set the desired
humidity set point by turning the dial stem flat to the corresponding set point indicated on the face of the unit.
This humidity control unit will operate the compressor and circulation fan when the dehumidification system is
activated, working only when there is a call, or demand for dehumidification.
Wiring
Unit Schematic
Blower InterLock Connections (Low Voltage)
Fan Coil / Air Handler
Control Thermostat (Typ)
G
W
Y
Existing Field Supplied
Control Wiring (Typ)
Field Supplied Control Wiring
Disconnect Existing Control Wiring
From Fan (G) Control Terminal
Reconnect to Blue Wire From DVA
Connect Brown Wire From DVA
To Fan (G) Terminal
Org Brn
Blu
GT
GF
RF
R C D
G Gt Gf Rf
*
Remove Jumper for Independent Fan Control
R
Close on RH Rise
Optional Humidistat
*
R
G
W
Y
Air Handler
DH 70
Return Air
Supply Air
Out Side Air (OSA) Hood
Manual OSA Damper
24 Volt Motorized Damper
( Power Open- Spring Closed)
With Bug Screen
(Volume Adjustment)
Optional Outside Air Ventilation