Introduction
Power Supply Front Panel Layout
1.4 Power Supply Unit Front Panel Layout
The power supply front panel contains the input ON/OFF circuit breaker
and the FAULT, MASTER / STANDALONE and SLAVE indicators. Refer
to Figure 1-2 and Table 1-3. for a description of front panel controls and
indicators.
Figure 1-2.
Model 4Q06125PS Front Panel
Table 1-3.
Power Supply Front Panel Controls and Indicators
Reference
(Figure Fig-
Control or Indi-
cator
Function
1
POWER ON/OFF
circuit breaker
switch
Applies source power to unit
2
SLAVE indicator
Not used for single power supply configuration of Model
4Q06125PS
3
MASTER indicator
Lights when configured as Model 4Q06125PS single
supply
4
FAULT indicator
Lights red when a fault is detected. The following failure
or fault conditions can cause the FAULT indicator to light:
overtemperature, instant internal overcurrent, output
overvoltage/overcurrent, local ±15V failure, input under/
overvoltage, input overcurrent, internal output under/
overvoltage, internal output overcurrent, overtempera-
ture, fan failure.
When the FAULT indicator lights, an audible beep
sounds a warning for approximately two seconds and the
output is crowbarred by an internal contactor. The fault is
latched. After the cause of the fault is removed, the unit
can be restarted by cycling the POWER circuit breaker to
OFF, then ON, or by applying a START_EXT pulse at
Analog I/O Port pin 7