Connecting the External Time Signal

If external signal(s) are required, the addition of a relay (not supplied) will be necessary.
Please consult your local electrician.

When a signal is activated the internal contacts close completing the circuit. These internal

contacts are “dry” and supply no voltage. Voltage applied to these contacts must not exceed

30 volts. An external relay must be used to activate signaling devices.

Recommended Relays: (Or similar line voltage switching relays)

1) Acroprint P/N 01-0230-000 (Grainger P/N 2E866)

2) Grainger 2E866 (HoneyWell RA89A1074)

3) Grainger 2E553 (White-Rogers 809A-189)

120VAC

External

Relay

External

Signal

Device

ES900

Internal

Relay

30V

Class 2

1

2

4

T

T

Connections Shown for HoneyWell RA89A1074

Neutral

Hot

Neutral

Amendment (Rev. B)