Xantrex Technology Xantrex Battery Monitor User Manual
Page 18
9
When all the necessary changes are made and checked in the setup
mode, you can jump back to the normal operating mode by pressing
the SETUP key for three seconds. Your Xantrex Battery Monitor is
now ready for use.
F17
Display (backlight) mode. Duration of backlight
activation in seconds after pressing a key on the Xantrex
Battery Monitor. The backlight can also be set to be
always ON or always OFF. In the setting AU the backlight
will be activated automatically when the charge/
discharge current exceeds 1 A or when a key is pressed.
Default
Range
Step size
30 seconds
OFF / 10 – 60 / ON
/ AU
10 seconds
F18
Alarm relay contact polarity. This Function enables
selection between a normally open (NO) or normally
closed (NC) contact. Please note that the NC setting will
slightly increase the Xantrex Battery Monitor’s supply
current in normal operating mode.
Default
Range
NO
NO, NC
F19
Firmware version. Displays the firmware version of the
Xantrex Battery Monitor. No alterations can be made.
Default
x.xx
F20
Setup lock. When this Function is ON, all functions
(except this one) are locked and cannot be altered.
Default
Range
OFF / ON
OFF