Xantrex Technology Xantrex Battery Monitor User Manual
Page 14

5
F02
Voltage charged parameter. The battery voltage must be
above this voltage level to consider the battery as fully
charged. Make sure the voltage charged parameter is
always slightly below the voltage at which the charger
finishes charging the battery (usually 0.1 V or 0.2 V below
the “float” stage voltage of the charger).
Default
Range
Step size
13.2 V
8.0 – 33.0 V
0.1 V
F03
Current charged parameter. When the charge current
value is below this percentage of the battery capacity (see
F01), the battery can be considered as fully charged.
Make sure the current charged parameter is always
greater than the minimum current at which the charger
maintains the battery, or stops charging.
Default
Range
Step size
2.0%
0.5 – 10.0%
0.5%
F04
Charged parameter time. This is the time the charged
parameters (as described in F02 and F03) must be met in
order to consider the battery as fully charged.
Default
Range
Step size
4 minutes
1 – 4 minutes
1 minute
F05
Low-battery alarm ON (discharge floor). When the state-
of-charge percentage has fallen below this value, the
alarm relay will be activated and the CHARGE BATTERY
indication will flash on the display to indicate the battery
must be charged. The time-to-go calculation and the
state-of-charge bar graph are also linked to this value. It
is recommended to keep this value at or around 50.0%.
Default
Range
Step size
50.0%
0.0 – 99.0%
1.0%