Status LED

Purpose

INV/CHRG

(Inverter/Charg

Power on light. It will be illuminated whenever the
power switch is on (inverter on) or when there is
incoming AC power and the charger comes on.

AC Input

Illuminates when incoming AC power has been
applied and the transfer relays have engaged.
There is a 7-12 second delay from the time the AC
is applied and this LED illuminates.

Steady

Overload

Indicates an over-temperature condition, the unit is
shut down. It will reset automatically after cooling.

Blinking

Overload

Inverter mode- Shutdown, diagnose problem using
DC Amps bar graph. Charger mode- Thermal
shutdown, after cooling reset by cycling power
switch.

Steady Battery

This is a High/Low Battery warning condition.
Inverter mode: Battery > 15.25 or < 10.50 volts
Charger mode: Battery > 15.25 or < 10.00 volts

Blinking

Battery

Indicates either a shutdown or equalizing.
Battery > 15.50 volts, will auto-reset at 15.25.
Inverter mode: Battery < 10.00 volts, will auto reset
at charger float voltage or upon AC input.
Charger mode: Battery < 8.00 volts for 1 minute,
remove all DC loads and manually reset by cycling
the power switch.