Technical information, Factory settings, Menu – Optima Company 600 - 1700 User Manual
Page 35: Advanced menu
35
Technical information
Technical information
Factory settings
The table displays the factory values (F value) of the
settings that you, as a customer, (K) can change via the
customer menus Menu and Advanced menu.
Read the table as follows:
To fi nd the settings for Holiday go to the Advanced menu,
select Temperature, then select Time limited settings and
then Holiday.
Menu
Level
F value
Temperature increase/decrease
K
=
(no change)
Room temperature setting
K
20ºC
Extra hot water
K
0 h
Advanced menu
Level
F value
Temperature
Heating system temperature
----"----\Heat curve
K
V=20,0ºC
H=55,2ºC
----"----\Hysteresis
----"----\----"----\Maximum
K
16ºC
----"----\----"----\Minimum K
4ºC
----"----\----"----\Time factor
K
10
Room sensor settings (T5)
----"----\Room temperature setting
K
20ºC
----"----\Room sensor infl uence
----"----\----"----\Change factor
K
5
----"----\----"----\Blocking time
K
4 h
Time limited settings
----"----\Time control heating
K
Off
----"----\----"----\Day and time
K
----"----\----"----\Change in temperature
K
-10ºC
----"----\Holiday
K
Off
----"----\----"----\Date
K
----"----\----"----\Change in temperature
K
-10ºC
Heating season
----"----\Heating season limit
K
18ºC
----"----\Delay
K
4 h
----"----\Direct start limit
K
10ºC
Heating, maximum operating time at hot
water requirement
K
20 min
Advanced menu
Level
F value
Hot water (T3)
Extra hot water
----"----\Number of hours
K
0
----"----\Stop temperature
K
65ºC
Hot water peak
----"----\ Interval
K
0 days
----"----\Start time
K
03:00
Time control hot water
K
Off
Setting the clock
Set date
K
Set time
K
Alarm
Alarm log
----"----\Delete alarm log?
K
No
Access level
K
0
Return to factor y settings
K
No
Deactivate alarm buzzer
K
No
Program version
K
xx.xx.x