2-2 Planning Your Site

Equipment Location

When planning your facilities, the following guidelines must be considered:

!

Does the allocated space allow for the proper installation of the
equipment and the performance of operation and maintenance activities?

!

Are the environmental conditions suitable for reliable operation?

!

Is the construction of the floor appropriate for the weight of the
equipment being installed?

!

Will the air conditioning maintain adequate temperature and humidity
conditions for the equipment being installed?

!

Are the proper electrical facilities available and adequate for the
equipment being installed?

!

Will future expansion be necessary or possible?

To plan your facilities, you must know your system configuration.

Space Requirements

The system rack requires an area that can:

!

Accommodate the height of the cabinet, which is 78.7 inches, (2 meters).

!

Provide a clearance above the rack of 16 inches (400 mm).

The space requirements of the area surrounding a single cabinet are given in
Figure 2-1. Note that the overall width should be increased by 23.4 inches for
each additional cabinet that is required by your system.