TP-6516 4/09

19

Section 1 Installation

1.6 Fuel Requirements

The generator set operates using natural gas or LP
vapor fuel. The generator set is EPA-certified for both
natural gas and LP vapor fuels.

The fuel system installation must comply with the NEC
and local codes.

1.6.1

Fuel Supply

Because

of

variable

climates

and

geographical

considerations, contact the local fuel supplier for fuel
system planning and installation. Figure 1-10 lists the
recommended fuel ratings and other fuel supply
information for natural gas and LP vapor fuels.

Fuel types

Natural Gas

LP Vapor

Fuel supply inlet

1/2 NPT

Fuel supply pressure,
kPa (in. H

2

O), 12 kW

1.3--2.7 (5-11)

1.7--2.7 (7-11)

Fuel supply pressure,
kPa (in. H

2

O), 17/18 kW

1.7--2.7 (7-11)

Fuel flow rate, Btu/hr.,
12 kW

193000

203000

Fuel flow rate, Btu/hr.,
17/18 kW

242000

280000

Nominal Fuel Rating, Btu/ft

3

Natural gas

1000

LP vapor

2500

Figure 1-10 Fuel Supply

Verify that the output pressure from the primary gas
utility (or LP tank) pressure regulator is within the range
shown in Figure 1-10 and that the utility gas meter flow
rate is sufficient to supply the generator set at rated load
plus all other gas-consuming appliances.

See

Figure 1-11 or Figure 1-12 for fuel consumption.
Contact the fuel supplier for flow rate information or a
gas meter upgrade.

See Figure 1-2 or Figure 1-4 for the location of the fuel
inlet connection. Use flexible sections to prevent fuel
line breakage caused by vibration.

Hold the fuel

solenoid valve with a wrench when tightening the fuel
connections. Protect all fuel lines from machinery or
equipment contact, adverse weather conditions, and
environmental damage.

Fuel Consumption at % Rated Load

Natural Gas, m

3

/hr. (cfh)

100%

5.9 (209)

75%

4.8 (168)

50%

3.6 (127)

25%

2.4

(85)

LP Vapor, m

3

/hr. (cfh)

100%

3.1 (108)

75%

2.5

(87)

50%

1.9

(65)

25%

1.2

(44)

LP vapor conversion factors:

8.58 ft.

3

= 1 lb.

0.535 m

3

= 1 kg

36.39 ft.

3

= 1 gal.

Nominal fuel rating:

Natural gas:

37 MJ/m

3

(1000 Btu/ft.

3

)

LP vapor:

93 MJ/m

3

(2500 Btu/ft.

3

)

Figure 1-11 Fuel Consumption, 12 kW Models

Fuel Consumption at % Rated Load

Natural Gas, m

3

/hr. (cfh)

100%

6.9 (242)

75%

5.8 (204)

50%

4.4 (155)

25%

3.4 (120)

LP Vapor, m

3

/hr. (cfh)

100%

3.2

(112)

75%

2.7

(96)

50%

2.1

(74)

25%

1.6

(57)

LP vapor conversion factors:

8.58 ft.

3

= 1 lb.

0.535 m

3

= 1 kg

36.39 ft.

3

= 1 gal.

Nominal fuel rating:

Natural gas:

37 MJ/m

3

(1000 Btu/ft.

3

)

LP vapor:

93 MJ/m

3

(2500 Btu/ft.

3

)

Figure 1-12 Fuel Consumption, 17/18 kW Models