TP-6516 4/09

18

Section 1 Installation

1.4.1

Exhaust Requirements

Carbon monoxide.
Can

cause

severe

nausea,

fainting, or death.

The

exhaust

system

must

be

leakproof and routinely inspected.

WARNING

Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust
fumes when working on or near the generator set. Never
operate the generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawn into a potentially occupied building through windows, air
intake vents, or other openings.

The exhaust system is complete for generator sets
installed outdoors.

Do not install this generator set

indoors.

Figure 1-6 gives the exhaust flow and temperature at
rated load.

The engine exhaust mixes with the

generator set cooling air at the exhaust end of the
enclosure.

Mount the generator set so that the hot

exhaust does not blow on plants or other combustible
materials. Maintain the clearances shown in Figure 1-5.

Exhaust System

60 Hz

Exhaust flow at rated kW,
m

3

/min. (cfm)

12 kW

3.8 (135)

17/18 kW

5.3 (187)

Exhaust gas temperature exiting
the enclosure at rated kW,

_C (_F)

216 (420)

Figure 1-6

Exhaust Flow and Temperature

1.4.2

Air Requirements

The generator set requires correct air flow for cooling
and combustion. The inlet and outlet openings in the
sound enclosure provide the cooling and combustion
air. Figure 1-7 shows the locations of the cooling air
intake and exhaust vents. Inspect the air inlet and outlet
openings inside and outside the housing to ensure that
the air flow is not blocked.

GM51561

2

1. Exhaust outlet
2. Alternator air intake (both sides)
3. Engine air intake

3

1

3

Figure 1-7

Cooling Air Intake and Exhaust

Model

Air Requirements,

m

3

/min. (cfm)

Hz

Cooling

Air

Combustion

Air

Total Inlet

Air

12 kW

60

26.9 (950)

1.1 (39.2)

28.0 (990)

50

22.4 (790)

0.9 (32.6)

23.4 (826)

17/18
kW

60

28.0 (989)

1.62 (57.3)

29.6 (1045)

50

22.6 (798)

1.42 (50.1)

24.0 (848)

Figure 1-8

Air Requirements

1.5 Power Supply

Power must be supplied from a source that is GFCI
protected to the generator set location for the battery
charger and the optional carburetor heater.

See

Section 1.8.

Connect power from a circuit on the

essential loads panel to the 120-VAC receptacles.
Figure 1-9 lists the power requirements for the battery
charger and accessories.

Equipment

Power Requirement, Max.

Watts

Amps

Volts

Battery charger

192

1.6

120

Carburetor heater:

12 kW

38

0.32

17/18 kW

40

0.34

Battery heater

110

0.92

Figure 1-9

Power Requirements