Figure 6 – Superior SSDVPF-CNE-B User Manual

Page 7

background image

7

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS

Figure 6

Minimum Clearances

Canadian Installation *

US Installation **

A = Clearance above grade, veranda, porch, deck

or balcony.

12 inches (30 cm) *

12 inches (30 cm) **

B = Clearance to window or door that may be

opened.

6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
12 in. (30 cm) for appliances > 10,000 BTU/hr (3kW) and <

100,000 BTU/hr (30kW), 36 inches (91 cm) for appliances
> 100,000 BTU/hr (30kW)*

6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW),
9 in. (23 cm) for appliances > 10,000 BTU/hr (3kW) and <

50,000 BTU/hr (15kW), 12 inches (30 cm) for appliances
> 50,000 BTU/hr (15kW)*

C = Clearance to permanently closed window

12 inches (305 mm) recommended to prevent window

condensation

9 inches (229 mm) recommended to prevent window

condensation

D = Vertical clearance to ventilated soffit located

above the terminal within a horizontal distance of 18
in. (458 mm) from the center line of the terminal

18 inches (458 mm)

18 inches (458 mm)

E = Clearance to unventilated soffit

12 inches (30 cm)

12 inches (30 cm)

F = Clearance to outside corner

5 inches (12.7 cm)

5 inches (12.7 cm)

G = Clearance to inside corner

2 inches (5.08cm) minimum - SV4.5HT-2 •

2 inches (5.08cm) minimum - SV4.5HT-2 •

H = Clearance to each inside of center line extended

above meter / regulator assembly

3 feet (91 cm) within a height of 15 feet above the meter /

regulator assembly *

3 feet (91 cm) within a height of 15 feet above the meter

/ regulator assembly **

I = Clearance to service regulator vent outlet

3 feet (91 cm) *

3 feet (91 cm) **

J = Clearance to non-mechanical air supply inlet

to building or the combustion air inlet to any other
appliance

6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 12

in. (30 cm) for appliances > 10,000 BTU/hr (3kW) and <
100,000 BTU/hr (30kW), 36 inches (91 cm) for appliances
> 100,000 BTU/hr (30kW)*

6 in. (15.2 cm) for appliances < 10,000 BTU/hr (3kW), 9

in. (23 cm) for appliances > 10,000 BTU/hr (3kW) and <
50,000 BTU/hr (15kW), 12 inches (30 cm) for appliances
> 50,000 BTU/hr (15kW)*

K = Clearance to mechanical air supply inlet

6 feet (1.8 meters) *

3 feet (91 cm) above, if within 10 feet (3 m) horizon-

tally**

L = Clearance above paved sidewalk or paved

driveway located on public property

7 feet (2.13 m) ‡

7 feet (2.13 m) ‡

M = Clearance under veranda, porch, deck or

balcony

12 in. (30 cm) * ‡

12 in. (30 cm) ** ‡

N = Depth of Alcove (Maximum

6 feet (1.83m) *

6 feet (1.83m) **

O = Clearance to Termination (Alcove)

6 inches (15.2mm)*

6 inches (15.2mm)**

P = Width of Alcove (Minimum)

3 feet (91cm)*

3 feet (91cm)**

Q = Clearance to Combustible Above (Alcove)

18 inches (457mm)*

18 inches (457mm)**

* In accordance with the current CSA-B149.1 National Gas and B149.2 Propane Installation Code - Latest Editions.

** In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Codes - Latest Edition.
‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
*‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor.

V

V

V

V

V

F

C

Fixed

Closed

Window

Operable

Window

B

B

A

B

H

M

I

= Area where Termination is not Permitted

= Air Supply Inlet

X

= Vent Termination

V

D

V

3 ft.

3 ft.

A

A

A

= 9” in U.S.

= 12” in Canada

V

L

B

J

X

V

A

G

Inside

Corner Detail

B

C

C

C

*18”

Ventilated Soffit

Horizontal

Termination

Detail D

Exterior Wall

6”

Inside Corner

*

See Item D in the Text Below.

V

P

V

O

N

N

Q

NOTE: Local Codes Or Regulations

May Require Different Clearances.

NOTE: Location Of The Vent Termination

Must Not Interfere With Access To The

Electrical Service.

E

K

X